Compute PFDavg and SIL classification for safety instrumented functions per IEC 61508 / IEC 61511.
Compute PFDavg and SIL classification for safety instrumented functions per IEC 61508 / IEC 61511 simplified formulas. Low demand mode only — safety function demanded < 1/year.
PFDavg
—
SIL Achieved
—
Risk Reduction Factor
—
Independent failures: —
Common cause (β): —
Detected failures contribution (MTTR): —
λdu (undetected): —
λdd (detected): —
MTTFd ≈ 11.4 years
Single channel, no redundancy.
Fraction of dangerous failures detected by auto-diagnostics.
Time from failure detection to repair completion.
Fraction of failures affecting all redundant channels simultaneously.
Failure rate decomposition:
Selected architecture:
• Low demand mode: safety function is demanded < 1 per year.
• Simplified formulas assume constant failure rate and perfect proof testing. For high-demand or continuous mode, use PFH instead.
• Detected failures contribute λdd × MTTR during the repair period.
• RRF (Risk Reduction Factor) = 1 / PFDavg.
Disclaimer
This calculator uses simplified formulas from IEC 61508-6 for educational and preliminary design purposes. For certified safety analysis, consult the full standard, vendor data sheets, and a qualified functional safety engineer. High-demand / continuous mode requires PFH calculation, not PFDavg.