Conductor Ampacity Lookup

CSA C22.1:24 Tables 1–4 ampacity for copper and aluminum conductors. Includes ambient temperature correction (Table 5A) and conduit fill adjustment (Table 5C). Updated for the 2024 code cycle — values unchanged from 2021, but mm² size column was removed and heading wording changed from "Allowable ampacities" to "Ampacities".

Inputs

Base temperature: 30°C (Table 5A correction applies)

Table 5C correction for 4+ current-carrying conductors

Results

Base Ampacity (Table 2/4)

amperes

Temp Correction

— A after correction

Fill Correction

— A after correction

Corrected Ampacity

amperes (after all corrections)

OESC Reference

Table 2 (Cu, 75°C)

How It Works

Tables 1–4: Table 1 covers copper conductors in free air, Table 2 covers copper in raceway/cable, Table 3 covers aluminum in free air, and Table 4 covers aluminum in raceway/cable. Each table has columns for 60°C, 75°C, and 90°C insulation ratings.

Table 5A (Temperature Correction): When ambient temperature differs from 30°C, ampacity is corrected by a factor. For temperatures above 30°C, ampacity decreases. For temperatures below 30°C, ampacity increases (up to a limit).

Table 5C (Conductor Fill): When 4+ current-carrying conductors are bundled in a raceway or cable, ampacity is reduced: 4-6 conductors → 80%, 7-24 → 70%, 25-42 → 60%, 43+ → 50%.

Reference Tables

Table 1 — Single Copper Conductors in Free Air

Ampacities for single copper conductors, bare/covered/insulated, ≤5000 V, unshielded, in free air. Ambient 30°C. See Rules 4-004, 4-006, 26-142, 42-008, 42-016, Tables 5A, 5B, 19.

Size (AWG/kcmil) 60°C 75°C 90°C 110°C 125°C 200°C
14 253035404050
12 303540454555
10 405055656580
8 6070809095115
6 8095105120130155
4 105125140160170205
3 120145165185195240
2 140170190215230280
1 165195220245265320
0 195230260290310375
00 220265300335355435
000 260310350390420510
0000 300360405455485590
250 340405455510545
300 370445500560600
350 425505570640680
400 455545615690735
500 520620700785835
600 580690780870930
700 6307558509551020
750 6557858859901060
800 68081592010301100
900 73087098011001175
1000 785935105511801260
1250 890106512001345
1500 985117513251485
1750 1070128014451620
2000 1160138515601750

* See Table 5A for correction factors at ambient temps over 30°C. See Table 5B for 2–4 conductors in contact. 2024 change: "Allowable ampacities" heading shortened to "Ampacities". mm² column removed.

Table 2 — ≤3 Insulated Copper Conductors in Raceway/Cable

Ampacities for not more than three insulated copper conductors, ≤5000 V, unshielded, in raceway or cable. Ambient 30°C. See Rules 4-004, 26-142, 42-008, 42-016, Tables 5A, 5C, 19, D3.

Size (AWG/kcmil) 60°C 75°C 90°C 110°C 125°C 200°C
14 152025253035
12 202530303540
10 303540454560
8 405055656580
6 5565758090110
4 708595105115140
3 85100115125135165
2 95115130145155190
1 110130145165175215
0 125150170190200245
00 145175195220235290
000 165200225255270330
0000 195230260290310380
250 215255290320345
300 240285320360385
350 260310350390420
400 280335380425450
500 320380430480510
600 350420475530565
700 385460520580620
750 400475535600640
800 410490555620660
900 435520585655700
1000 455545615690735
1250 495590665745
1500 525625705790
1750 545650735820
2000 555665750840

* See Table 5A for ambient temp correction, Table 5C for 4+ current-carrying conductors.

Table 3 — Single Aluminum Conductors in Free Air

Ampacities for single aluminum conductors, bare/covered/insulated, ≤5000 V, unshielded, in free air. Ambient 30°C. See Rules 4-004, 26-142, 42-008, 42-016, Tables 5A, 5B, 19.

Size (AWG/kcmil) 60°C 75°C 90°C 110°C 125°C 200°C
12 253035404050
10 354045505565
8 455560707590
6 65758595100125
4 85100115125135165
3 95115130145155190
2 115135150170180220
1 130155175195210255
0 150180205225245295
00 175210235265285345
000 200240270305325395
0000 235280315355375460
250 265315355400425
300 295350395440470
350 330395445500535
400 355425480535575
500 405485545615655
600 455545615690735
700 500595670750800
750 520620700785835
800 540645725815870
900 585700790885945
1000 6307508459501010
1250 7158559651080
1500 79595010701200
1750 880105011851325
2000 965115012951455

Table 4 — ≤3 Insulated Aluminum Conductors in Raceway/Cable

Ampacities for not more than three insulated aluminum conductors, ≤5000 V, unshielded, in raceway or cable. Ambient 30°C. See Rules 4-004, 26-142, 42-008, 42-016, Tables 5A, 5C.

Size (AWG/kcmil) 60°C 75°C 90°C 110°C 125°C 200°C
12 152025252535
10 253035404050
8 354045505565
6 405055657080
4 5565758090105
3 65758595100125
2 7590100115120150
1 85100115125135165
0 100120135150160195
00 115135150170180220
000 130155175195210255
0000 150180205225245295
250 170205230260275
300 195230260290310
350 210250280315335
400 225270305340365
500 260310350390420
600 285340385430460
700 315375425475505
750 320385435485520
800 330395445500535
900 355425480535575
1000 375445500560600
1250 405485545615
1500 435520585655
1750 455545615690
2000 470560630710

Table 5A — Ambient Temperature Correction Factors

Correction factors for Tables 1, 2, 3, 4, and 60 at ambient temperatures above 30°C. See Rules 4-004 7) and 16-330.

Ambient °C 60°C 75°C 90°C 105°C 110°C 125°C 150°C 200°C 250°C
35 0.910.940.960.970.970.970.980.990.99
40 0.820.880.910.930.940.950.960.970.98
45 0.710.820.870.890.900.920.940.950.97
50 0.580.750.820.860.870.890.910.940.95
55 0.410.670.760.820.830.860.890.920.94
60 0.580.710.770.790.830.870.910.93
65 0.470.650.730.750.790.840.890.92
70 0.330.580.680.710.760.820.870.90
75 0.500.630.660.730.790.860.89
80 0.410.580.610.690.760.840.88
90 0.450.500.610.710.800.85
100 0.260.350.510.650.770.83
110 0.400.580.730.80
120 0.230.500.690.77
130 0.410.640.74
140 0.290.590.71

2024 note: Column references shifted from "3 to 8" (2021) to "2 to 7" (2024) due to mm² size column removal in Tables 1–4.